Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Full Load Efficiency
91 %
Full Load Pf
83
Open End Bearing
6206
Rotation
R
Washdown Duty
No
Motor Shaft Size
1 1/8 in
Enclosure Designation
XPFC - Explosion Proof Fan Cooled
Frame
215T
Useable at 208V
No
Mounting Style
F-1
C Dimension
19.91 in
Hz
60 Hz, 50 Hz
RPM
1800 rpm, 1500 rpm
Design
A
Voltage
190/380/230/460
Type
X0750M
Frame Size
Shaft Input, Not a C-Face
Drive End Bearing
6307
Phase
Three Phase
Enclosure
XPFC
Full Load rpm
1460 rpm, 1760 rpm
RefPicture
EM7064T
VoltCode
U
Service Factor
1
Efficiency Group
Premium Efficient
Full Load Amps
12.5
Motor Shaft Length
3 in
Brake Feature
No
Product Line
RG
BALD Family Names
Premium Efficient, Explosion Proof
Motor Application
Explosion Proof
Mounting
Rigid Base
Mult. Sym.
L1
Voltage Rating
190, 460, 230, 380
Poles
4
Weight
252.0 LB
EAN or UPC
781568220313
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back