Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Full Load rpm
3540 rpm
Frame
364TS
BALD Family Names
Premium Efficient, Nema Premium™
Epact Nominal Full Load Efficiency
93 %
Frame Material
Steel
Poles
2
Type
4254M
Drive End Bearing
6313
Motor Shaft Size
1 7/8 in
Frame Size
Shaft Input, Not a C-Face
Voltage
230/460
Efficiency Group
Premium Efficient
C Face Kit
14-1401
Washdown Duty
No
Voltage Rating
460, 230
Motor Application
General Purpose
Hz
60 Hz
Mounting
Rigid Base
Mounting Style
F-1
Service Factor
1.15
VoltCode
F
Enclosure Designation
OPSB - Open Slotted Band
Full Load Amps
82
Full Load Efficiency
94.5 %
Phase
Three Phase
Motor Shaft Length
3 3/4 in
Mult. Sym.
L1
Rotation
R
Useable at 208V
No
RefPicture
ODP3P
Product Line
RG
RPM
3600 rpm
C Dimension
27.56 in
Enclosure
OPSB
Design
B
Full Load Pf
91
Substitute Motor
M2549T
Brake Feature
No
Open End Bearing
6311
Weight
507.0 LB
EAN or UPC
781568105283
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back