Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Mounting
Rigid Base
Motor Shaft Size
1 7/8 in
Mult. Sym.
L1
Frame
364TS
Service Factor
1.15
Drive End Bearing
6313
BALD Family Names
Premium Efficient, Nema Premium™
Poles
2
C Face Kit
14-1401
RefPicture
ODP3P
Rotation
R
Full Load Amps
82
Washdown Duty
No
Mounting Style
F-1
Phase
Three Phase
Open End Bearing
6311
Brake Feature
No
Hz
60 Hz
Design
B
RPM
3600 rpm
Frame Material
Steel
Efficiency Group
Premium Efficient
Useable at 208V
No
C Dimension
27.56 in
Voltage Rating
460, 230
Voltage
230/460
Enclosure Designation
OPSB - Open Slotted Band
Full Load Pf
91
Epact Nominal Full Load Efficiency
93 %
VoltCode
F
Frame Size
Shaft Input, Not a C-Face
Type
4254M
Enclosure
OPSB
Full Load rpm
3540 rpm
Substitute Motor
M2549T
Product Line
RG
Full Load Efficiency
94.5 %
Motor Shaft Length
3 3/4 in
Motor Application
General Purpose
Weight
507.0 LB
EAN or UPC
781568105283
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back