Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Motor Application
General Purpose, Premium Efficient
Enclosure
OPSB
Full Load rpm
1775 rpm
RefPicture
EMDP
Full Load Pf
85
Rotation
R
BALD Family Names
Premium Efficient, Nema Premium™
Service Factor
1.15
VoltCode
H
RPM
1800 rpm
Poles
4
Useable at 208V
No
Substitute Motor
M2539T-5
Product Line
RG
Efficiency Group
Premium Efficient
Mult. Sym.
L1
Voltage
575
Type
4250M
Frame Size
Shaft Input, Not a C-Face
Hz
60 Hz
Drive End Bearing
6312
Open End Bearing
6311
Mounting
Rigid Base
Frame
324T
Full Load Amps
37.4
Phase
Three Phase
Mounting Style
F-1
Design
B
Full Load Efficiency
94.5 %
Brake Feature
No
Voltage Rating
575
Enclosure Designation
OPSB - Open Slotted Band
Washdown Duty
No
Weight
482.0 LB
EAN or UPC
781568118764
NEMA Premium
My Applied Catalog
We're here for you