Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Service Factor
1.15
Efficiency Group
Premium Efficient
Full Load Amps
35
Full Load Efficiency
94.1 %
Enclosure
OPSB
Full Load rpm
1770 rpm
Drive End Bearing
6311
Rotation
R
Motor Shaft Size
1 7/8 in
RPM
1800 rpm
Poles
4
Frame Size
Shaft Input, Not a C-Face
Enclosure Designation
OPSB - Open Slotted Band
Washdown Duty
No
Open End Bearing
6309
Mult. Sym.
L1
Phase
Three Phase
Motor Shaft Length
4 5/8 in
RefPicture
EMDP
BALD Family Names
Premium Efficient, Nema Premium™
Voltage Rating
460, 230
Frame
286T
C Dimension
25.06 in
VoltCode
E1
C Face Kit
40-1400
Epact Nominal Full Load Efficiency
92.4 %
Hz
60 Hz
Design
B
Voltage
230/460
Motor Application
General Purpose
Mounting
Rigid Base
Substitute Motor
M2535T
Brake Feature
No
Useable at 208V
Yes
Full Load Pf
85
Product Line
RG
Type
4052M
Mounting Style
F-1
Frame Material
Steel
Weight
372.0 LB
EAN or UPC
781568105054
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back