Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Full Load Pf
92
RefPicture
EMTECI
Efficiency Group
Premium Efficient
VoltCode
H
Mult. Sym.
L1
Frame Material
Cast Iron
Frame Size
Shaft Input, Not a C-Face
Type
0954M
Mounting Style
F-1
Useable at 208V
No
BALD Family Names
Premium Efficient, Nema Premium™
Frame
286TS
Drive End Bearing
6311
Full Load Efficiency
93 %
Washdown Duty
No
Motor Shaft Size
1 5/8 in
Substitute Motor
M4108T-5
Service Factor
1.15
Brake Feature
No
Full Load Amps
26.2
Enclosure Designation
TEFC - Totally Enclosed Fan Cooled
Motor Shaft Length
3 1/4 in
Voltage Rating
575
Motor Application
General Purpose
RPM
3600 rpm
Rotation
R
Enclosure
TEFC
Hz
60 Hz
C Dimension
26.39 in
Product Line
RG
C Face Kit
10-1305
Design
A
Open End Bearing
6208
Poles
2
Full Load rpm
3520 rpm
Voltage
575
Phase
Three Phase
Mounting
Rigid Base
Weight
418.0 LB
EAN or UPC
781568139127
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back