Motors misapplied in hazardous environments can cause a fire or explosion, resulting in destruction of property, serious injury or death
Only the end user or a qualified underwriter is to identify and select the proper class, group, division and temperature code motor to meet the requirements of each installation
Service center personnel can advise what listings and approvals motors carry, but cannot evaluate nor recommend what motors may be suitable for use in hazardous environments
Type
3944M
Enclosure
OPSB
RPM
1800 rpm
Frame Size
Shaft Input, Not a C-Face
Voltage Rating
460, 230
Mult. Sym.
L1
Enclosure Designation
OPSB - Open Slotted Band
Washdown Duty
No
Brake Feature
No
Motor Application
General Purpose
Full Load Pf
86
Phase
Three Phase
Rotation
R
Efficiency Group
Premium Efficient
Drive End Bearing
6309
Full Load Amps
23.5
RefPicture
EMDP
Useable at 208V
Yes
Mounting Style
F-1
BALD Family Names
Premium Efficient, Nema Premium™
Poles
4
Substitute Motor
M2515T
VoltCode
E1
Motor Shaft Size
1 5/8 in
Voltage
230/460
Open End Bearing
6208
Full Load Efficiency
93 %
Motor Shaft Length
4 in
Product Line
RG
Frame
256T
Service Factor
1.15
Mounting
Rigid Base
Epact Nominal Full Load Efficiency
91 %
Design
B
Full Load rpm
1765 rpm
C Face Kit
39-1400
Frame Material
Steel
Hz
60 Hz
Weight
225.0 LB
EAN or UPC
781568104910
NEMA Premium
My Applied Catalog
We're here for you
with Service Centers across the country - We have your back